Yamile Diaz Torres*
Study Center of Energy and Environment, University Carlos Rafael Rodríguez, Cuba
*Corresponding author:Study Center of Energy and Environment, University Carlos Rafael Rodríguez, Cienfuegos, Cuba
Submission: September 02, 2021;Published: September 28, 2021
ISSN 2640-9690 Volume3 Issue5
A chiller plant is a complex HVAC system. Its main feature is that it uses water as a heat
transfer fluid, extracts heat from the medium, and thus lowers the air temperature through
a heat transfer process. These systems offer many advantages over direct expansion systems
in terms of operation, reliability and efficiency. The initial investment is approximately 2.2
times greater than individual air conditioning systems, but the comfort achieved is superior
and also provides quieter operation and enhances the internal and external aesthetics of the
building. Thermal distribution requires less space compared to All-Air systems, making it very
suitable for buildings with limited space. They allow simultaneous control of different thermal
zones as well as air conditioning and heating circuits. They are usually used in facilities that
have significant air conditioning needs, such as large hotels, restaurants, cinemas, theatres,
shopping centres, hospitals and other public buildings. They are usually installed when the
building is constructed, although in some cases they are installed when existing buildings
are remodelled. Chillers or “chillers” (technical terminology) are the central axis of a system,
which in turn consists of several machines and is responsible for 60% of energy consumption
[1].
Efficient design of a chiller system, based on proper selection of its components, can
reduce energy consumption. According to Fang et al. [2], when a system is improperly
designed, the efficiency of each element in the system deviates from its optimal operation.
They also affirm that poor design of a chiller system is a common problem in engineering.
For example, in a study by Gang et al. [3], changing the total number of chillers as well as the
distribution of cooling capacity between chillers allows up to 69% variability in consumption.
The asymmetric configuration of chillers of different capacities allows a saving of 10.1%
according to the study presented by Yu & Chan [4]. Kapoor & Edgar [5] found that chillers
configured in series consume 9.62% more energy than those configured in parallel. Lee & Lee
[6] showed that the increase of chillers of the same capacity in a plant favors the increase of
efficiency and decrease of energy consumption. The redundancy of chillers ensures additional
load on the cooling load in case of failure in the system, which largely provides robustness.
For example, Wang et al. [7] determined a significant increase in the failure rate of a nonredundant
system over a redundant one, from 1.3 *10-6 to 2.4 * 10-2. As can be seen, different
decisions applied to the design of the chiller units made a difference in the energy efficiency
of the system.
The design of chillers refers to the determination of the cooling capacity of the systems
and their configuration. The configuration must consider the total capacity of the system, the
number of chillers to be installed, the arrangement of cooling capacity between chillers, and the hydraulic arrangement. But is it enough to achieve an efficient
design using only the standards or recommendations established in
the field, or does it only help us to establish basic design of a chiller
plant?
For example, a conventional plant design suggested by ASRHAE
Fundamentals [8] indicates that the total capacity of the plant is
approximately 15% higher than the peak demand resulting from
the thermal load calculation. This safety factor is used to avoid the
risk of undersizing. On the other hand, there is another criterion
used by ASHRAE Standard 90.1-2010 [9] that affects the total
capacity of the installation, which specifies that the unmet hours
cannot exceed 300 hours. Regarding the number of chillers to be
installed, it is generally stated that a system must consist of N +
1 chillers to ensure system reliability. Taylor [10] points out that
there are installations that are critical is required to install usually
N + 1 or N + 2 redundant chillers, taking into account the possibility
that the chiller with the larger capacity fails. Only one chiller is
unacceptable for most facilities, especially where the use of these
systems is vital (laboratories, data centres, hospitals, hotels, etc.).
On the other hand, Yu & Ho [11] report that a large capacity facility
must contain at least three chillers. However, space constraints may
influence the decision.
Cooling capacity between chillers is another of the decisions
that are predetermined. ASHRAE 90.1-2013 [12] (Table G3.1.3.7)
recommends the use of a symmetrical arrangement according to
the cooling needs of the building. On the other hand, Yu & Chan
[13] state as a rule that four to eight chillers should be used in
buildings with cooling demand between 1050-7032kW. A similar
statement is made by Chan et al. [1]. Stanford [14], recommends
the use of asymmetric configurations composed of 80% -20% of
the total capacity and the other is 60% -40%. This last split was
first advocated by Haviland & CEM [15] under the criterion that in
applications such as hotels and offices, chillers can operate more
than 50% at part load. Another suggestion was made by Matheu
& Greenberg [16] who propose a ratio of 30% -70% in the case
of laboratories. Finally, in the case of hydraulic arrangement
Kapoor & Edgar [5], the parallel configuration is recommended
because it allows the operation of the number of chillers that is
really needed, depending on the heat demand of the building.
Moreover, it allows the continuous operation of one of the chillers
in case of maintenance or unexpected failure of the other, ensuring
uninterrupted operation.
These aforementioned rules allow us to have a starting point
to create an initial design of the chiller, which can serve as a basic
structure for comparing multiple combinations that come from
different methods or studies conducted by the researcher. It is
important to realize that it is not the plant that defines the building,
but rather the opposite. It is the building that defines the operation
of the air conditioning system. Therefore, the decision on the
arrangement to be set up must be based on a thorough study of the
thermal dynamics of the facility. Some studies based on the analysis
of the thermal requirements of a facility in operation allow us to
identify interesting modes of investigation that should be applied in
the early stages of the design. For example, Deng [17], Cheng et al.
[18] and Wang et al. [19], in their studies proposed a modification
of the existing configuration. However, these decisions have an
economic cost due to the initial inefficiency.
Therefore, estimating the variation of the thermal demand that
the installation will have should be the main task of the engineer. In
the new design procedure for chiller installations, it is necessary to
consider not only the construction of a demand profile that reflects
the worst operating conditions, but also to elaborate several
profiles that incorporate the uncertainties of the demand. For
this, the stochastic method can be used or otherwise, knowing the
variables of utilisation of similar plants, assuming work schedules,
percentage of occupancy, variations of the degree’s days of the place
and simulating, through the different thermodynamic programmes
using deterministic methods, profiles of thermal demands and at
the wide working regime to which the chiller can be subjected.
Finally, to conclude this extensive search and creation of data, a deep
statistical analysis that helps to determine the prevailing cooling
capacities and thus create different chiller configurations. Then,
using creative mathematical algorithms, different configurations
are created from the result by changing the total cooling capacity of
the plant and the number of chillers [20,21].
The design phase of a chiller system should be the maximum
saving point for the system. It is time for engineers to waste
creativity. In this sense, it is also suggested that the energy analysis
should not be done by traditional methods but use mathematical
optimization to take into account the use of automatic control
systems and operational measures that affect energy efficiency. It
is a challenge, but from an economic and energy point of view, it is
worthwhile not to limit oneself to the rules dictated by technology,
but also to expand engineering knowledge.
© 2021 Yamile Diaz Torres. This is an open access article distributed under the terms of the Creative Commons Attribution License , which permits unrestricted use, distribution, and build upon your work non-commercially.